  • Description
    • Insulation resistance measurement:
      • measurement voltage any in the range of 50…1000 V at 10 V and 1000...5000 V at 25 V resolution,
      • continuous indication of measured insulation resistance or leakage current,
      • automatic discharge of measured object capacitive voltage after the end of insulation resistance measurement,
      • acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics,
      • metered T1 , T2 and T3 test times for measuring one or two absorption coefficients from the range of 1…600 s,
      • adjustable measuring time to 99'59'’,
      • polarization index (PI) and dielectric absorption ratio (DAR) measurement,
      • indication of actual test voltage during measurement,
      • 1.2 mA and 3 mA test current,
      • step voltage insulation resistance measurement (SV),
      • Dielectric Discharge calculation (DD),
      • protection against measuring live objects,
      • measurements with test leads up to 20 m.
    • Digital filters function for measurements in high noise enviroment (10 s, 30 s , 60 s).
    • Measurement of leakage current during insulation resistance testing.
    • Measurement of capacitance during the measurement of RISO.
    • DC and AC voltage measurement in the range of 0…600 V.
    • 990 cells of memory (11880 records) with the capability of wireless data transmission to a PC or through a USB cable.
    • Power supply from battery packs, low battery warning indicator, built-in fast charger.
    • Display backlit.

    The instruments meet the requirements of the EN 61557 standard.

    Remote control by phone.

  • Technical Specification

    Insulation resistance measurement (two-lead)

    Measurement range acc. to IEC 61557-2: 50k…15,0 TΩ (IISOnom = 1,2 mA or 3 mA)

    Range Resolution Accuracy
    0,0...999 kΩ 1 kΩ ±(3% m.v. + 10 digits)
    1,00...9,99 MΩ 0,01 MΩ ±(3% m.v. + 10 digits)
    10,0...99,9 MΩ 0,1 MΩ ±(3% m.v. + 10 digits)
    100...999 MΩ 1 MΩ ±(3% m.v. + 10 digits)
    1,00...9,99 GΩ 0,01 GΩ ±(3% m.v. + 10 digits)
    10,0...99,9 GΩ 0,1 GΩ ±(3% m.v. + 10 digits)
    100...999 GΩ 1 GΩ ±(3,5% m.v. + 10 digits)
    1,00...9,99 TΩ 0,01 TΩ ±(7,5% m.v. + 10 digits)
    10,0...15,0 TΩ 0,1 TΩ ±(10% m.v. + 10 digits)

    Values of measured resistance depending on measurement voltage

    Voltage UISO Measurement range
    250 V 500 GΩ
    500 V 1,00 TΩ
    1000 V 2,00 TΩ
    2500V 5,00 TΩ
    5000V 15,0 TΩ

     

    Measurement of leakage current

     

    Range Resolution Accuracy
    0…ILmax m, µ, n [A] Calculation based on resistance measures

    · ILmax – maximum current at short circuit of leads,
    · resolution and units result from the measurement range of individual insulation resistance.

    Step voltage insulation resistance measurement

    Target voltage Measurement voltage sequence
    1 kV 200, 400, 600, 800, 1000 V
    2,5 kV 0,5, 1, 1.5, 2, 2,5 kV
    5 kV 1, 2, 3, 4, 5 kV

    · duration of each "step" adjustable from 30s to 5mins
    · measurement result for each voltage step is stored in memory

    Capacity measurement

    Range Resolution Accuracy
    1...999 nF 1 nF ±(5% m.w. + 5 digits)
    1,00...49,99 µF 0,01 µF ±(5% m.w. + 5 digits)

    · Capacity measurement result is displayed after the RISO measurement

    DC and AC voltage measurement

    Range Resolution Accuracy
    0.0...29,9 V 0,1 V ±(2% m.v. + 20 digits)
    30,0...299,9 V 0,1 V ±(2% m.v. + 6 digits)
    300...600 V 1 V ±(2% m.v. + 2 digits)
     

    The acronym “m.v.” stands for a “measured reference value”.