MPI-505
- Description
Product withdrawn from the offer
Measurement of short-circuit loop parameters:
- in L-PE, L-N, L-L circuits as well as in L-PE (RCD) circuits - without tripping RCD breakers of current 30 mA.
- impedance measurement of short-circuit loops in power networks of nominal voltages: 115/200 V, 220/380 V, 230/400 V, 240/415 V and frequencies in the range of 4565 Hz..
Testing of AC and A types residual current circuit breakers:
- testing of regular and selective residual current circuit breakers of nominal differential currents: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA,
- IA trip current measurement,
- tA trip time measurement for 0.5In, In, 2In, 5In,
- measurement of earth continuity and touch voltage without tripping RCDs,
- functionality of automatic measurement of residual current circuit breaker parameters.
Measurement of insulation resistance at voltages: 100 V, 250 V, 500 V and 1000 V.
Low-voltage measurement of resistance, protective connections and equipotential bonding:
- measurement of continuity of protective connections with current ±200 mA,
- automatic calibration of test leads - capability of using any test leads,
- measurement of resistance with low current and acoustic signaling.
Quick verification of correctness of the PE wire connection with a touch probe.
Measurement of AC voltage.
Indication of phase sequence.
Memory of 990 measurements, data transfer to a PC over the USB interface
- Technical Specification
Display range Resolution Accuracy 0,00...19,99 Ω 0,01 Ω ±(5% m.v +3 digits) 20,0...199,9 Ω 0,1 Ω ±(5% m.v +3 digits) 200...1999 Ω 1 Ω ±(5% m.v +3 digits) Display range Resolution Accuracy 0,00...19,99 Ω 0,01 Ω ±(6% m.v + 10 digits) 20,0...199,9 Ω 0,1 Ω ±(6% m.v + 5 digits) 200...1999 Ω 1 Ω ±(6% m.v + 5 digits) Display range*) Resolution Accuracy 0...1999 kΩ 1 kΩ ±(3% m.v. + 8 digits) 2,00...19,99 MΩ 0,01 MΩ ±(3% m.v. + 8 digits) 20,0...199,9 MΩ 0,1 MΩ ±(3% m.v. + 8 digits) 200...500 MΩ 1 MΩ ±(3% m.v. + 8 digits) 200...1000 MΩ 1 MΩ ±(3% m.v. + 8 digits) 200...1999 MΩ 1 MΩ ±(3% m.v. + 8 digits) 2,00...3,00 GΩ 0,01 GΩ ±(4% m.v. + 6 digits) Range Resolution Accuracy 0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits) 20,0...199,9 Ω 0,1 Ω ±(2% m.v. + 3 digits) 200...400 Ω 1 Ω ±(2% m.v. + 3 digits) RCD type Test current multiplier Range Resolution Accuracy Standard 0,5*IΔn 0...300 ms 1 ms ± (2% m.v. + 2 digits) Standard 1*IΔn 0...300 ms 1 ms ± (2% m.v. + 2 digits) Standard 2*IΔn 0...150 ms 1 ms ± (2% m.v. + 2 digits) Standard 5*IΔn 0...40 ms 1 ms ± (2% m.v. + 2 digits) Selective 0,5*IΔn 0...500 ms 1 ms ± (2% m.v. + 2 digits) Selective 1*IΔn 0...500 ms 1 ms ± (2% m.v. + 2 digits) Selective 2*IΔn 0...200 ms 1 ms ± (2% m.v. + 2 digits) Selective 5*IΔn 0...150 ms 1 ms ± (2% m.v. + 2 digits) Selected current Measurement range Resolution Test current Accuracy 10 mA 3,3...10,0 mA 0,1 mA 0,3xIΔn...1,0xIΔn ± 5% IΔn 30 mA 9,0...30,0 mA 0,1 mA 0,3xIΔn...1,0xIΔn ± 5% IΔn 100 mA 33...100 mA 1 mA 0,3xIΔn...1,0xIΔn ± 5% IΔn 300 mA 90...300 mA 1 mA 0,3xIΔn...1,0xIΔn ± 5% IΔn 500 mA 150...500 mA 1 mA 0,3xIΔn...1,0xIΔn ± 5% IΔn 1000 mA 330...1000 mA 1 mA 0,3xIΔn...1,0xIΔn ± 5% IΔn Selected current Measurement range Resolution Test current Accuracy 10 mA 4...20,0 mA 0,1 mA 0,35 x IΔn ...2,0 x IΔn ±10% IΔn 30 mA 12,0...42,0 mA 0,1 mA 0,35xIΔ..1,4xIΔn ±10% IΔn 100 mA 40,0...140 mA 1 mA 0,35xIΔ..1,4xIΔn ±10% IΔn 300 mA 120...420 mA 1 mA 0,35xIΔ..1,4xIΔn ±10% IΔn 500 mA 200...700 mA 1 mA 0,35xIΔ..1,4xIΔn ±10% IΔn “m.v” - measurement value
- Files
- Sonel Reader (current version)changelog
Changes in version 4.0.11.0 compared to the previous one:
- Fixed numbering truncation during printouts.
- Improved MIC-2511 tests display.
- Added ability to change the order of tests in PAT meter self-tests.